  • Operating Voltage: 15 – 32VDC
  • Maximal consumption: 470 μА @ 27VDC
  • Humidity resistance: (93 ± 3)% @ +40°C
  • Color: White
  • Material: SAN, transparent
  • Dimensions: 102 x 70mm
SKU: 32020011 Category:

Description

Addressable Sounder Strobe Base

The SensoIRIS BSOU is аn addressable fire base with built-in sounder in its body. SensoIRIS BSOU is designed for installing in addressable fire alarm systems supporting TTE communication protocol. The device is powered on from the panel and can be controlled via the communication protocol. The addressable SensoIRIS BSOU fire base supports 32 different tone types at two sound levels. The tone type and sound level are programmed from the control panel. The device is designed for easy installation and consist from two parts: mounting plane basis and sounder with factory mounted fire base

The SensoIRIS BSOU is compatible for operation with TTE addressable detectors series: HD1, SD1 and HSD1. The device is designed for easy installation and consists from two parts: mounting plane basis and sounder is a body with factory mounted fire base.

Installation Instructions
Attention: Power off the loop circuit before installing the addressable fire base!
1.Choose the proper place for installation of the device.
2. Set the device address directly from addressable fire panel. The address must be in the range from 1 to
250.
3. Fix the mounting plane basis on the ceiling of the protected premises using fixings according the mounting surface.
4. Run the loop wires and fix the sounder body to the mounting basis using the supplied screws in the spare parts kit.
5. Connect the fire base to the fire panel using the wiring diagram.
6. Insert a detector – HD1/ SD1/ HSD1 – into the fire base and rotate clockwise until it drops into place – the short mark on
the base fits with that on the sounder body. Continue to rotate the detector until its mark coincides with the long mark on the base – a
click is heard.
Note: The mounted detector base is assigned at different address to the control panel!
7. Program the sounder parameters. Refer to the Programming manual of the control panels.
8. Test the sounder for proper operation

The Addressable Sounder Strobe Base has the following specifications and features:-

Operating Voltage Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 – 32VDC
Maximal consumption at communication . . . . . . . . . . . . . . . . . 470 μА @ 27VDC
Maximal consumption:
– main tone type 27, low volume level . . . . . . . . . . . . . . . . . 3 mА @ 27VDC
– main tone type 27, high volume level. . . . . . . . . . . . . . . . . 10 mА @ 27VDC
Power volume (main tone type 27):
– low volume. . ~ 88dB (A) ± 3dB @ 1m
– high volume . . ~ 96dB (A) ± 3dB @ 1m
Power volume (other tone types):
– low volume. . 82-92dB ± 3dB @ 1m
– high volume. . 90-100dB ± 3dB @ 1m
Frequency of the strobe flashing . . . . . . . . . . . . . . . . . . . . . . . . 1Hz
Number of tone types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
2 Wire Gauge for terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0,4 – 2.0mm
Relative humidity resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . (93 ± 3)% @ +40°C
Color . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . White
Material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SAN, transparent
Dimensions with mounted detector . . . . . . . . 102 x 70mm