SensoIRIS Gas LPG/CH14 Detector, 24VDC-3W 31020049
SensoIRIS GAS is a gas detector suitable for application in addressable fire alarm systems, supporting TTE communication protocol. SensoIRIS GAS is designed for detection of leaking natural gas (LNG) and leaking petroleum gas (LPG). The detector is equipped with alarm output for management of manipulator or electromagnetic valve. Gas detector is suitable for wall mounting using metal hanger included in the supplied equipment. Fully programmable from the fire alarm panel.
SensoIRIS Gas LPG/CH14 Detector, 24VDC-3W 31020049
SensoIRIS GAS is addressable gas, LPG and CH4 (Methane), leakage detector. When flammable gas is present in concentrations, higher than the dangerous, threshold alarm level is activated. Red indicator lights on and buzzer is turned on. Gas detector has auto diagnostic function. It continuously checks sensor and electronics status. If problem with sensor or electronics yellow LED is activated, green LED blinks and sound signal is activated.
– If short pressed “SILENCING” mode is activated. Green LED flashes, buzzer and panel activation are disabled for 5min;
– If pressed for more than 5 seconds “TEST” mode is activated. In this case green, red and yellow LED’s are activated. Panel and buzzer are activated, too. After 6 seconds gas detector emits 2 short sounds and leaves “TEST” mode.
Gas detector has auto diagnostic function. It continuously checks sensor and electronics status. If problem with sensor or electronics yellow LED is activated, green LED blinks and sound signal is activated. The LPG is heavier than air and the detector should be placed at height from the room floor between 0.3 -1.0m.
– The CH4 (Methane) is lighter than air and the detector should be placed at height from the room ceiling between 0.3 – 1.0m.
– The distance from the detector to the gas source for the both mentioned above cases should not exceed 1.5m
Do not use the following substances near to the device:
– solvents and diluents;
– alcohol, fuels;
– silicones products and colors;
– perfumes;
– cleaning detergents;
– spray products
When alarm stops it is necessary to find gas leaking cause. If alarm persists and the leak can not be found, vacate the premise and immediately inform the gas emergency service.
WARNING:
– Installation and wiring of gas detector must be made by qualified technician with compliance with the current standards.
– Before wiring this gas detector turn mains power off.
– To ensure correct operation periodic functional check is advisable. In order to check the proper efficiency of the device sensor a specific test gas bottle must be used. Any other method for testing, such as the use of cigarette lighters or flammable substances can lead to wrong conclusions and damage the sensor.